Bit Hex Dec
Alarm word
(parameter 1
6-90 Alarm
Word)
Alarm word 2
(parameter 1
6-91 Alarm
Word 2)
Alarm word
3
(parameter 1
6-97 Alarm
Word 3)
Warning
word
(parameter 16
-92 Warning
Word)
Warning
word 2
(parameter 16
-93 Warning
Word 2)
Extended
status word
(parameter 16
-94 Ext. Status
Word)
Extended
status word 2
(parameter 16-95 Ex
t. Status Word 2)
0
000000
01
1 Brake check Reserved
STO function
fault
Reserved Reserved Ramping O
1
000000
02
2
Pwr. card
temp
Gate drive
voltage fault
MM alarm
Pwr. card
temp
Reserved AMA tuning Hand/Auto
2
000000
04
4 Earth Fault Reserved Reserved Earth fault Reserved Start CW/CCW Probus OFF1 active
3
000000
08
8
Ctrl. card
temp
Reserved Sync. fault
Ctrl. card
temp
Reserved Slowdown Probus OFF2 active
4
000000
10
16 Ctrl. word TO Reserved Reserved Ctrl. word TO Reserved Catch up Probus OFF3 active
5
000000
20
32 Overcurrent Reserved Reserved Over current Reserved Feedback high Reserved
6
000000
40
64 Torque limit Reserved Reserved Torque limit Reserved Feedback low Reserved
7
000000
80
128
Motor Th.
over
Reserved Reserved
Motor Th.
over
Reserved
Output
current high
Control ready
8
000001
00
256
Motor ETR
over
Broken belt Reserved
Motor ETR
over
Broken belt
Output
current low
Drive ready
9
000002
00
512
Inverter
overld.
Reserved Reserved
Inverter
overld.
Reserved
Output freq.
high
Quick stop
10
000004
00
1024
DC under
volt.
Start failed Reserved
DC under
volt.
Reserved
Output freq.
low
DC brake
11
000008
00
2048 DC over volt. Speed limit Reserved DC over volt. Reserved
Brake check
ok
Stop
12
000010
00
4096 Short circuit
External
interlock
Reserved Reserved Reserved Braking max Reserved
13
000020
00
8192 Reserved Reserved Reserved Reserved Reserved Braking
Freeze output
request
14
000040
00
16384
Mains ph.
loss
Reserved Reserved Mains ph. loss Reserved Reserved Freeze output
15
000080
00
32768 AMA not ok Reserved Reserved No motor
Auto DC
braking
OVC active Jog request
16
000100
00
65536
Live zero
error
Reserved Reserved Live zero error Reserved AC brake Jog
17
000200
00
131072 Internal fault Reserved Reserved Reserved Reserved Reserved Start request
18
000400
00
262144
Brake
overload
Reserved Reserved
Brake resistor
power limit
Reserved Reserved Start
19
000800
00
524288 U phase loss Reserved Reserved Reserved Reserved
Reference
high
Reserved
20
001000
00
1048576 V phase loss
Option
detection
Reserved Reserved Overload T27 Reference low Start delay
21
002000
00
2097152 W phase loss Option fault Reserved Reserved Reserved Reserved Sleep
22
004000
00
4194304 Fieldbus fault Locked rotor Reserved Fieldbus fault
Memory
module
Reserved Sleep boost
Troubleshooting
VLT
®
Midi Drive FC 280
126 Danfoss A/S © 03/2016 All rights reserved. MG07C202
6
6