Danfoss VLT Midi Drive FC-280P4K0 [94/136] Midi drive fc 280

Danfoss VLT Midi Drive FC-280P2K2 [94/136] Midi drive fc 280
16-60 Digital Input
Range: Function:
0* [0 -
65535 ]
View the actual state of the digital inputs 18, 19,
27, 29, 32, and 33.
Bit 0 Digital input terminal 33
Bit 1 Digital input terminal 32
Bit 2 Digital input terminal 29
Bit 3 Digital input terminal 27
Bit 4 Digital input terminal 19
Bit 5 Digital input terminal 18
Bit 6–15 Unused
Table 4.6 Bits Denition
16-61 Terminal 53 Setting
Shows the setting of input terminal 53.
Option: Function:
[1] Voltage mode
[6] Digital input
16-62 Analog Input 53
Range: Function:
1* [0 - 20 ] View the actual value at input 53.
16-63 Terminal 54 Setting
Option: Function:
View the setting of input terminal 54.
[0] Current mode
[1] Voltage mode
16-64 Analog Input AI54
Range: Function:
1* [0 - 20 ] View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range: Function:
0 mA* [0 - 20
mA]
View the actual value at output 42. The
value shown reects the selections in
parameter 6-90 Terminal 42 Mode and
parameter 6-91 Terminal 42 Analog Output.
16-66 Digital Output
Range: Function:
0* [0 - 15 ] View the binary value of all digital outputs.
16-67 Pulse Input #29 [Hz]
Range: Function:
0* [0 - 130000 ] View the actual frequency rate on terminal 29.
16-68 Pulse Input 33 [Hz]
Range: Function:
0* [0 - 130000 ] View the actual value of the frequency
applied at terminal 33 as an impulse input.
16-69 Pulse Output 27 [Hz]
Range: Function:
0* [0 - 40000 ] View the actual value of impulses applied to
terminal 27 in digital output mode.
16-71 Relay Output
Range: Function:
0* [0 - 65535 ] View the settings of all relays.
16-72 Counter A
Range: Function:
0* [-32768 -
32767 ]
View the present value of counter A. Counters are
useful as comparator operands, see
parameter 13-10 Comparator Operand.
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital Inputs),
or by using an SLC action (parameter 13-52 SL
Controller Action).
16-73 Counter B
Range: Function:
0* [-32768 -
32767 ]
View the present value of counter B. Counters are
useful as comparator operands
(parameter 13-10 Comparator Operand).
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital Inputs)
or by using an SLC action (parameter 13-52 SL
Controller Action).
16-74 Prec. Stop Counter
Range: Function:
0* [0 - 2147483647] Shows the current value of the precise
stop counter.
16-80 Fieldbus CTW 1
Range: Function:
0* [0 -
65535 ]
View the 2-byte control word (CTW) received
from the bus master. Interpretation of the CTW
depends on the eldbus option installed and the
CTW prole selected in parameter 8-10 Control
Word Prole. For more information, see relevant
eldbus manuals.
16-82 Fieldbus REF 1
Range: Function:
0* [-32768 -
32767 ]
To set the reference value, view the 2-byte
word sent with the control word from the
bus master. For more information, refer to
the relevant eldbus manual.
Parameter Descriptions
VLT
®
Midi Drive FC 280
92 Danfoss A/S © 03/2016 All rights reserved. MG07C202