Danfoss VLT Midi Drive FC-280P4K0 [57/136] Notice

Danfoss VLT Midi Drive FC-280P2K2 [57/136] Notice
5-19 Terminal 37/38 Safe Torque O
Use this parameter to set up the STO functionality. Warning
makes the frequency converter coast and enables automatic
restart. Alarm makes the frequency converter coast and requires
a manual restart.
Option: Function:
[1] * Safe Torque O
Alarm
Coasts the frequency converter
when Safe Torque O is activated.
Manual reset from LCP, digital input,
or eldbus.
[3] Safe Torque O
Warning
Coasts the frequency converter
when Safe Torque O is activated
(terminal 37 and terminal 38 o).
When Safe Torque O circuit is
reestablished, the frequency
converter continues without manual
reset.
4.6.2 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminal
27. Set the I/O function for terminal 27 in
parameter 5-01 Terminal 27 Mode.
Terminal 42 can also be congured as digital outputs.
NOTICE
These parameters cannot be adjusted while the motor is
running.
5-30 Digital Outputs
[0] No operation Default for all digital outputs.
[1] Control ready The control card is ready.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready /
remote control
The frequency converter is ready for
operation and is in auto-on mode.
[4] Stand-by / no
warning
Ready for operation. No start or stop
command is given (start/disable). No
warnings are active.
[5] Running The motor is running and shaft torque is
present.
[6] Running / no
warning
The output speed is higher than the
speed set in parameter 1-81 Min Speed for
Function at Stop [RPM]. The motor is
running and there are no warnings.
[7] Run in range /
no warning
The motor is running within the
programmed current and speed ranges
set in parameter 4-50 Warning Current Low
to parameter 4-51 Warning Current High.
There are no warnings.
[8] Run on
reference / no
warning
The motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output. There are
no warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque limit The torque limit set in
parameter 4-16 Torque Limit Motor Mode
or parameter 4-17 Torque Limit Generator
Mode has been exceeded.
[12] Out of current
range
The motor current is outside the range
set in parameter 4-18 Current Limit.
[13] Below current,
low
The motor current is lower than set in
parameter 4-50 Warning Current Low.
[14] Above current,
high
The motor current is higher than set in
parameter 4-51 Warning Current High.
[15] Out of
frequency
range
Output frequency is outside the
frequency range.
[16] Below
frequency, low
The output speed is lower than the
setting in parameter 4-40 Warning Freq.
Low.
[17] Above
frequency, high
The output speed is higher than the
setting in parameter 4-41 Warning Freq.
High.
[18] Out of
feedback range
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low and
parameter 4-57 Warning Feedback High.
[19] Below feedback
low
The feedback is below the limit set in
parameter 4-56 Warning Feedback Low.
[20] Above
feedback high
The feedback is above the limit set in
parameter 4-57 Warning Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[22] Ready, no
thermal
warning
The frequency converter is ready for
operation, and there is no overtem-
perature warning.
[23] Remote, ready,
no thermal
warning
The frequency converter is ready for
operation and is in auto-on mode. There
is no overtemperature warning.
[24] Ready, no
overvoltage/
undervoltage
The frequency converter is ready for
operation and the mains voltage is within
the specied voltage range (see chapter
General Specications in the design guide).
[25] Reverse The motor runs (or is ready to run)
clockwise when logic=0 and counter-
clockwise when logic=1. The output
changes when the reversing signal is
applied.
[26] Bus OK Active communication (no timeout) via
the serial communication port.
[27] Torque limit
and stop
Use in performing a coast stop and in
torque limit condition. If the frequency
Parameter Descriptions Programming Guide
MG07C202 Danfoss A/S © 03/2016 All rights reserved. 55
4 4