Daikin FCQ71B7V3B [147/381] Restart standby

Daikin FCQ50B7V1 [147/381] Restart standby
ESIEN05-04 Functional concept
Part 2 Functional Description 2–9
3
2
4
5
1
1.6 Restart Standby
Outline To prevent the compressor from frequently turning ON and OFF and allow pressure equalization,
forced thermostat OFF will be conducted for 3 minutes after compressor stopping (compressor guard
timer).
Graph
Thermostat OFF
Compressor
Electronic expansion valve
Oudoor unit fan
ON
ON
OFF
OFF
OFF
Restart standby
complete
Residual
operation
For 3 minutes
Moves to “Stop” or
“Starting control” after
completion of “Restart
standby”.