Daikin RXYQ28PY1 [315/487] Central control equipment combinations

Daikin RXYQ40PY1 [315/487] Central control equipment combinations
ED34-645B Control System
Control 707
16
3.2.4 Central Control Equipment Combinations
The table below shows which combinations of central control equipment are possible and which are not.
1 The schedule timer cannot be used by itself. Use in combination with the central remote controller or unified ON
/ OFF controller.
2 May be used in combination if control range differs (up to 4 units).
3 May be used in combination if control range differs
(up to 8 units: Up to 16 units in the double central control mode).
4 May be used in combination if control range differs
(up to 2 units: Up to 4 units in the double central control mode).
5 The meaning of
{
, ×, — are as follows
{
: Possible Functions
×: Impossible Functions
—: No Functions
If using in combination with central control equipment, the relation between them is last command priority.
If using in combination with central control equipment, the remote control mode is decided by the setting of the
highest priority item in the priority rank shown in the table below.
Priority Ranking of Remote Control Mode Settings
Central
Remote
Controller
Unified
ON / OFF
Controller
Schedule
Timer
Wiring
Adaptor for
Electrical
Appendices
Parallel
Interface
Interface for
use in
BACnet
®
intelligent
Manager
Central Remote Controller
4
{{
×
{{{
Unified ON/OFF Controller {
3 { × {{{
Schedule Timer
1
{{
—× × × ×
Wiring Adaptor for Electrical
Appendices
××××××
Parallel Interface
{{
××—
×
Interface for use in BACnet
®
{{
××××
intelligent Manager
{{
××××
Interface for use
in BACnet
®
Parallel Interface
Central Remote
Controller
intelligent Touch
Controller
Unified ON/OFF
Controller
Schedule Timer
Priority Ranking112234