Daikin RXYQ28PY1 [353/487] Selection of control mode no

Daikin RXYQ42PY1 [353/487] Selection of control mode no
ED34-645B Control Devices
Control 745
16
4.3.8 Selection of Control Mode No.
Select whether to accept or to reject the operation from the remote controller regarding the operation, stop,
temperature setting and operation mode setting, respectively, and determine the particular control mode from the
right most column of the table below.
(Example)
C : 3P171361-1
Operation
mode
Control by remote controller
Control
mode
Operation
Stop
Temperature
control
Operation
mode setting
Unified operation, individual
operation by central remote
controller, or operation
controlled by timer
Unified stop, individual
stop by central remote
controller, or timer stop
ON/OFF control
impossible by
remote controller
Rejection
(Example)
Rejection
(Example)
Rejection
(Example)
Rejection
Acceptance 0
Rejection 10
Acceptance
(Example)
Acceptance
(Example)
1
(Example)
Rejection 11
Only OFF control
possible by
remote controller
Acceptance
Rejection
Acceptance 2
Rejection 12
Acceptance
Acceptance 3
Rejection 13
Centralized
Acceptance
Rejection
Acceptance 4
Rejection 14
Acceptance
Acceptance 5
Rejection 15
Individual Acceptance
Rejection
Acceptance 6
Rejection 16
Acceptance
Acceptance 7
Rejection 17
Timer operation
possible by
remote controller
Acceptance
(During timer at
ON position only)
Rejection
(During timer at OFF
position)
Rejection
Acceptance 8
Rejection 18
Acceptance
Acceptance 9
Rejection 19
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation
mode setting
by remote
controller
Temperature
control by
remote
controller
Stop by
remote
controller
[
Rejection
][
Rejection
][
Rejection
][
Acceptance
][
Acceptance
]
The control
mode is “ 1 ”.