4.3.6 Wiring Instructions
Wiring instructions
For control wiring of DIII-NET, you can select from the following 3 types of wiring methods.
1. Series method :
Wiring is connected by a single line from the central controller.
2. Bus method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
3. Star method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
Specifications of transmission wiring
Be sure to use either 2-core sheathed vinyl cord or cable as mentioned below. The size of wire should be selected in
the range of 0.75~1.25 mm².
When the shield wire is used, be sure to ground the one side of the shield wire.
<Length of control wiring>
Between central remote controller and air-conditioner
Maximum extension : 1,000 m, Total length : 2,000 m ()
When you have branches, be sure to make a total length of all the branch.
Vinyl cab tire round cord VCTF JISC 3306
Vinyl insulated, vinyl sheathed cable for control CVV JISC 3401
Round vinyl sheathed cable for control CVS JISC 3401
600V vinyl cab tire cable VCT JISC 3312
Polyethylene insulated vinyl sheathed cable () CPEV
Mesh insulated cable () MVVS