8 | Configuration
Installer reference guide
135
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
weather-dependent operation is active, the water temperature is determined
automatically depending on the outdoor temperature. Low outdoor temperatures
will result in warmer water and vice versa. During weather-dependent operation,
the user has the possibility to shift up or down the target water temperature by a
maximum of 10°C.
See the user reference guide and/or operation manual for more details about this
function.
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A LWT setpoint mode:
Fixed: The desired leaving water
temperature is:
- NOT weather-dependent (i.e. does NOT
depend on the outdoor ambient
temperature)
- fixed in time (i.e., NOT scheduled)
Weather dep. (default): The desired leaving
water temperature is:
- weather-dependent (i.e. depends on the
outdoor ambient temperature)
- fixed in time (i.e., NOT scheduled)
continued >>
# Code Description
[A.3.1.1.1] N/A << continuation
Fixed/scheduled: The desired leaving
water temperature is:
- NOT weather-dependent (i.e., does NOT
depend on the outdoor ambient
temperature)
- according a schedule. The scheduled
actions consists of desired shift actions,
either preset or custom.
Remark: This value can only be set in
leaving water temperature control.
WD/scheduled: The desired leaving water
temperature is:
- weather-dependent (i.e., does depend on
the outdoor ambient temperature)
- according a schedule. The scheduled
actions consists of desired leaving water
temperatures either preset or custom
Remark: This value can only be set in
leaving water temperature control.