8 | Configuration
Installer reference guide
143
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
# Code Description
N/A [C‑0A] Indoor quick heat up function
0 (default): OFF.
1: On.
Domestic hot water control
Only applicable in case an optional domestic hot water tank is installed.
This is always applicable for Switzerland.
Configuring the desired tank temperature
The domestic hot water can be prepared in 3 different ways. They differ from each
other by the way the desired tank temperature is set and how the unit acts upon it.
# Code Description
[A.4.1] [6-0D] Domestic hot water Type:
0 (Reheat only): Only reheat operation is
allowed.
1 (Reheat + sched.): The domestic hot
water tank is heated according to a schedule
and between the scheduled heatup cycles,
reheat operation is allowed.
2 (Scheduled only)(default): The domestic
hot water tank can ONLY be heated according
to a schedule.
See "Domestic hot water control: advanced"[4154] for more details.
INFORMATION
If a third‑party tank is present in the system ([E‑07]=6), it is recommended to set
[6‑0D] to "0" (i.e. Reheat only).
Maximum DHWtemperature setpoint
The maximum temperature that users can select for the domestic hot water. You
can use this setting to limit the temperatures at the hot water taps.
INFORMATION
During disinfection of the domestic hot water tank, the DHW temperature can
exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the applicable legislation.