Breadcrumb Field code Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
Setting name
A.2.1.8 [7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
A.2.1.9 [F-0D]
R/W 0: Continuous
1: Sample
2: Request
A.2.1.A [E-04]
R/O
1: Yes
A.2.1.B
R/W 0: At unit
1: In room
└─ Options
A.2.2.1 [E-05]
R/W
0: No
1: Yes
A.2.2.2 [E-06]
R/W
0: No
1: Yes
A.2.2.3 [E-07]
R/W
0~6
4: Type 5
6: Type 7
A.2.2.4 [C-05]
R/W 1: Thermo ON/OFF
2: C/H request
A.2.2.5 [C-06]
R/W
1: Thermo ON/OFF
2: C/H request
A.2.2.6.2 [D-07]
Digital I/O PCB Solar kit
R/W
0: No
1: Yes
A.2.2.6.3 [C-09]
Digital I/O PCB Alarm output
R/W
0: Normally open
1: Normally closed
A.2.2.7 [D-04]
R/W
0: No
1: Pwr consmp ctrl
A.2.2.8 [D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.A [D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
A.2.2.B [C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.2.2.C [D-0A]
R/W
0: Not present
1: 1 /m³
2: 10 /m³
3: 100 /m³
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
A.3.1.1.2.1 [9-01]
Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.1.2.2 [9-00]
Temperature range Maximum temp (heating) R/W 37~80°C, step: 1°C
80°C
A.3.1.1.2.3 [9-03]
Temperature range Minimum temp (cooling) R/W 5~18°C, step: 1°C
5°C
A.3.1.1.2.4 [9-02]
Temperature range Maximum temp (cooling) R/W
18~22°C, step: 1°C
22°C
A.3.1.1.5 [8-05]
R/W 0: No
1: Yes
A.3.1.1.6.1 [F-0B]
Shut-off valve Thermo On/OFF R/W
0: No
1: Yes
A.3.1.1.6.2 [F-0C]
Shut-off valve Cooling R/W 0: No
1: Yes
A.3.1.1.7 [9-0B]
R/W
0: Quick
1: Slow
└────────────────── Additional
A.3.1.2.1
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
A.3.1.2.2.1 [9-05]
Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.2.2.2 [9-06]
Temperature range
Maximum temp (heating) R/W 37~80°C, step: 1°C
80°C
A.3.1.2.2.3 [9-07]
Temperature range Minimum temp (cooling) R/W 5~18°C, step: 1°C
5°C
A.3.1.2.2.4 [9-08]
Temperature range Maximum temp (cooling) R/W 18~22°C, step: 1°C
22°C
└─ Room thermostat
A.3.2.1.1 [3-07]
Room temp. range Minimum temp (heating) R/W 12~18°C, step: A.3.2.4
12°C
A.3.2.1.2 [3-06]
Room temp. range Maximum temp (heating) R/W 18~30°C, step: A.3.2.4
30°C
A.3.2.1.3 [3-09]
Room temp. range Minimum temp (cooling) R/W 15~25°C, step: A.3.2.4
15°C
A.3.2.1.4 [3-08]
Room temp. range Maximum temp (cooling) R/W 25~35°C, step: A.3.2.4
35°C
A.3.2.2 [2-0A]
R/W -5~5°C, step: 0,5°C
0°C
A.3.2.3 [2-09]
R/W -5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 1°C
1: 0,5°C
└─ Operation range
A.3.3.1 [4-02]
R/W 14~35°C, step: 1°C
25°C
A.3.3.2 [F-01]
R/W 10~35°C, step: 1°C
20°C
└─ Domestic hot water (DHW)
└─ Type
Room temp. step
Space heating OFF temp
Space cooling On temp
LWT setpoint mode
Modulated LWT
Emitter type
LWT setpoint mode
Room temp. offset
Ext. room sensor offset
Contact type add.
Demand PCB
External kWh meter 1
DHW pump
External sensor
External gas meter
Power saving possible
User interface location
DHW operation
DHW tank
DHW tank type
Contact type main
Number of LWT zones
Pump operation mode
*HYHBH/X*AA/FV3 4P353731-1H - 2021.02