Daikin EHYHBX08AFV3 [60/252] Installation

Daikin EHYHBX08AFV3 [60/252] Installation
7 | Installation
Installer reference guide
60
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
283
580
<100
(mm)
<100
>300
In any case, provide at least 300 mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100 mm above the maximum expected
level of snow. In this case, it is recommended to construct a pedestal, and on this
pedestal install the EKFT008CA option kit.
283
580
<150
<150
(mm)
>300
100
a
b
a Maximum snowfall height
b EKFT008CA option kit
If the unit is installed on brackets to the wall, it is recommended to use the
EKFT008CA option kit and to install the unit as follows: