Daikin EHYHBX08AFV3 [63/252] To prevent the outdoor unit from falling over

Daikin EHYHBX08AFV3 [63/252] To prevent the outdoor unit from falling over
7 | Installation
Installer reference guide
63
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
If you install the unit on a frame, install a waterproof plate within 150mm of the
bottom side of the unit in order to prevent water from getting into the unit and
to avoid drain water dripping (see the following figure).
NOTICE
If the drain holes of the outdoor unit are blocked up, provide space of at least
300mm below the outdoor unit.
An additional drain pan kit (EKDP008CA) can be used to gather the drain water. The
drain pan kit consists of:
b
a
a Drain pan
b U-beams
283 mm
580 mm
7.3.6 To prevent the outdoor unit from falling over
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1 Prepare 2 cables as indicated in the following illustration (field supply).
2 Place the 2 cables over the outdoor unit.