ABB RLON-01 [68/82] Definition

ABB RLON-01 [68/82] Definition
Network variables
68
UCPTstopMode / nciStopMode
Definition:
Network config input SNVT_switch nciStopMode
UCPT type index: 6
Explanation:
Is used to select between coast and ramp stop.
Valid range:
OFF = COAST, ON = RAMP
Default value:
COAST
UCPTstopLevel / nciStopLevel
Definition:
Network config input SNVT_lev_percent nciStopLevel
UCPT type index: 7
Explanation:
Stop level value in ramp stop mode. When the speed of the drive
reaches this level, a coast stop is performed. The value is relative
to nvoDrvSpeed i.e. the value of 5% corresponds to nvoDrvSpeed
value 5%.
Valid range:
Valid range 5-100%
-163.84% .. 163.83% (0.005% or 50 ppm)
The value 0x7FFF represents invalid data.
Default value:
5%.