Daikin EWADC12C-XL [208/304] Evaporator water temperatures inverted

Daikin EWADC14C-PR [208/304] Evaporator water temperatures inverted
Alarms and Events ESIE10-01
3–8 Part 3 – Troubleshooting
3
1
3
4
5
1.2.4 Evaporator Water Temperatures Inverted
Alarm description (as shown on screen): Evap Water Inverted.
Trigger: [Evap EWT < Evap LWT - 1 deg C AND at least one circuit is running AND EWT sensor fault
not active AND LWT sensor fault not active] for 30 seconds.
Action Taken: Pumpdown stop on all circuits.
Reset: This alarm can be cleared manually via the keypad.