Daikin EWADC12C-XL [242/304] Suction temperature sensor fault

Daikin EWADС14C-PL [242/304] Suction temperature sensor fault
Alarms and Events ESIE10-01
3–42 Part 3 – Troubleshooting
3
1
3
4
5
1.4.24 Suction Temperature Sensor Fault
Alarm description (as shown on screen): SuctTempSensFault N.
Trigger: Sensor shorted or open.
Action Taken: Normal shutdown of circuit.
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.