Daikin EWADC12C-XL [243/304] Discharge temperature sensor fault

Daikin EWADC13C-XR [243/304] Discharge temperature sensor fault
ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–43
33
4
5
1
1.4.25 Discharge Temperature Sensor Fault
Alarm description (as shown on screen): DiscTempSensFault N.
Trigger: Sensor shorted or open.
Action Taken: Normal shutdown of circuit.
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.