Daikin EWADC12C-XL [230/304] Low oat restart fault

Daikin EWADC21C-XS [230/304] Low oat restart fault
Alarms and Events ESIE10-01
3–30 Part 3 – Troubleshooting
3
1
3
4
5
1.4.12 Low OAT Restart Fault
Alarm description (as shown on screen): LowOATRestart Fail N.
Trigger: Circuit has failed three low OAT start attempts.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.