Daikin EWADC12C-XL [209/304] Leaving evaporator water temperature sensor fault

Daikin EWADС14C-PS [209/304] Leaving evaporator water temperature sensor fault
ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–9
33
4
5
1
1.2.5 Leaving Evaporator Water Temperature Sensor Fault
Alarm description (as shown on screen): Evap LWT Sens Fault.
Trigger: Sensor shorted or open.
Action Taken: Rapid stop all circuits.
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.