Daikin EWADC12C-XL [232/304] No pressure at startup

Daikin EWADC11C-SS [232/304] No pressure at startup
Alarms and Events ESIE10-01
3–32 Part 3 – Troubleshooting
3
1
3
4
5
1.4.14 No Pressure At Startup
Alarm description (as shown on screen): No Press At Start N.
Trigger: [Evap Pressure < 5 psi OR Cond Pressure < 5 psi] AND Compressor start requested AND
circuit does not have a fan VFD.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.