Daikin EWADC12C-XL [235/304] Fc comm failure circuit 3

Daikin EWADC16C-SL [235/304] Fc comm failure circuit 3
ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–35
33
4
5
1
1.4.17 FC Comm Failure Circuit 3
Alarm description (as shown on screen): FC Comm Fail Cir 3.
Trigger: Number of Circuits set point is greater than 2 and communication with the I/O extension
module has failed.
Action Taken: Rapid stop of circuit 3.
Reset: This alarm can be cleared manually via the keypad when communication between main
controller and the extension module is working for 5 seconds.