Daikin EWADC12C-XL [226/304] High discharge temperature

Daikin EWADC12C-XL [226/304] High discharge temperature
Alarms and Events ESIE10-01
3–26 Part 3 – Troubleshooting
3
1
3
4
5
1.4.8 High Discharge Temperature
Alarm description (as shown on screen): Disc Temp High N.
Trigger: Discharge Temperature > High Discharge Temperature set point AND compressor is
running. Alarm cannot trigger if discharge temperature sensor fault is active.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.