Daikin EWADC12C-XL [225/304] Mechanical high pressure switch

Daikin EWADC15C-SS [225/304] Mechanical high pressure switch
ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–25
33
4
5
1
1.4.7 Mechanical High Pressure Switch
Alarm description (as shown on screen): Mech High Pressure Sw N.
Trigger: Mechanical High Pressure switch input is low AND Emergency Stop Alarm is not active.
(Opening emergency stop switch kills power to MHP switches).
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad if the MHP switch input is
high.