ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–31
33
4
5
1
1.4.13 No Pressure Change After Start
Alarm description (as shown on screen): NoPressChgAtStrt N.
Trigger: After start of compressor, at least a 1 psi drop in evaporator pressure OR 5 psi increase in
condenser pressure has not occurred after 15 seconds.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.