3–36 Part 3 – Troubleshooting
3
1
3
4
5
1.4.18 FC Comm Failure Circuit 4
Alarm description (as shown on screen): FC Comm. Fail Cir 4.
Trigger: Number of Circuits set point is greater than 3 and communication with the I/O extension
module has failed.
Action Taken: Rapid stop of circuit 4.
Reset: This alarm can be cleared manually via the keypad when communication between main
controller and the extension module is working for 5 seconds.