Daikin EWADC12C-XL [239/304] Evaporator pressure sensor fault

Daikin EWADC17C-SL [239/304] Evaporator pressure sensor fault
ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–39
33
4
5
1
1.4.21 Evaporator Pressure Sensor Fault
Alarm description (as shown on screen): EvapPressSensFault N.
Trigger: Sensor shorted or open.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.