Siemens 6SL3210-1SE27-5UA0 [90/318] Power modules blocksize 1 ph ac

Siemens 6SL3210-1SE23-2AA0 [90/318] Power modules blocksize 1 ph ac
Power Modules
3.1 Power Modules Blocksize (PM340)
Manual
90 Manual, 01/2011, 6SL3097-4AC10-0BP2
DANGER
Once the terminal cover has been removed, the degree of protection of the Power Module
is reduced to IP00.
Operation on non-grounded line supply systems (IT)
It is not permissible to use Power Modules with integrated line filter in IT line supply systems.
3.1.7 Technical data
3.1.7.1 Power Modules Blocksize, 1-ph. AC
Table 3- 9 Technical data PM340, 1-ph. AC
Line supply voltage 1-ph. 200 V to 240 V AC ±10%
PM340 6SL3210– 1SB11-0UA0 1SB12-3UA0 1SB14-0UA0
PM340 with integrated line filter 6SL3210– 1SB11-0AA0 1SB12-3AA0 1SB14-0AA0
Frame size FSA FSA FSA
Output current
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
Peak current l
max
A
A
A
A
0.9
0.8
1.4
2.0
2.3
2.0
3.3
4.6
3.9
3.4
5.5
7.8
Unit rating based on I
n
1)
kW 0.12 0.37 0.75
Rated pulse frequency kHz 4 4 4
Power loss kW 0.06 0.075 0.11
Cooling air requirement m
3
/s 0.005 0.005 0.005
Sound pressure level LpA (1 m) dB < 45 < 45 < 45
24 V DC supply
for the Control Unit
A 1.0 1.0 1.0
Rated input current
2)
without/with integrated line reactor
A
1.4 / 2.2
4 / 6
6.5 / 10
Class J UL safety fuses
Rated current
Rated short-circuit current SCCR
A
kA
6
65
10
65
15
65
Circuit breaker type designation
EN 60947
Rated current
A
5SJ4206-7HG41
6
5SJ4210-7HG41
10
5SJ4216-7HG41
16

Содержание