Daikin RXY32MY1 [77/125] Stopping leakage check by manual operation

Daikin RXY24MYLE [77/125] Stopping leakage check by manual operation
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
76
Executing a Leakage Check places the outdoor unit and indoor units registered in the same
refrigeration system under “Maintenance”. “Maintenance” is released upon Leakage Check
completion (If the iTM is stopped when the Leakage Check completes, “Maintenance” is
released at power recovery).
After staring Leakage Check, check that an appropriate indoor unit is “Under Maintenance”.
Also, upon completion of a Leakage Check run, check on the History screen if no
communication error has occurred with outdoor units and, if any error is found, run Leakage
Check again.
NOTE
Stopping Leakage Check by manual operation
Stop Leakage Check by manual operation.
(17)
(18)
1. Select the target outdoor unit from the Outdoor Unit list (17) and touch the Check Stop button
(18). A conrmation dialog appears. Touching the Yes button starts to check the target outdoor
unit and indoor units registered in the refrigeration system. If they are normal, the Leakage
Check for the outdoor unit is stopped. If a communication error occurs with the target outdoor
unit, the Leakage Check cannot be stopped.
When the Leakage Check stops, the “Maintenance” status placed on the outdoor unit and
indoor units registered in the same refrigeration system is released.
NOTE