Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
36
3. CSV le format
The format of the CSV le output from the iTM is as shown below. A CSV le output when no
management point data is registered can be used as a template for new implementations since
only the area used by the system and the header portion are output.
The following table shows the CSV format for management point data registration.
Numeric values indicated in each item correspond to the column number in the CSV le (the rst column is xed and used for data type
identication). Blank items indicate there is no applicable data.
Classication
Keyword Description Value
Management point type
Di Pi D3Di D3Dio
Indoor
unit
Outdoor
unit
Internal
Ai
Ventilator Chiller
Internal
Pi
BACnet
Di
BACnet
Dio
BACnet
Ai
BACnet
Ao
Common
Header type
identication
DI-H PI-H D3DI-H
D3DIO-H
IN-H OUT-H
INTERNAL
AI-H
HRV-H
CHIL-H
INTERNAL
PI-H
BACNET
DI-H
BACNET
DIO-H
BACNET
AI-H
BACNET
AO-H
Data type identication
DI-D PI-D D3DI-D
D3DIO-D
IN-D OUT-D
INTERNAL
AI-D
HRV-D
CHIL-D
INTERNAL
PI-D
BACNET
DI-D
BACNET
DIO-D
BACNET
AI-D
BACNET
AO-D
POINTID Management point ID 101 to 1000000 2
NAME Name
String (1 to 12 characters regardless of single or double byte)
3
DETAILEDINFO Detailed information
String (0 to 50 characters regardless of single or double byte)
4
PROHIBITOP
Prohibit manual
operation
0: Allowed, 1: Prohibited 5 5 5 5 5 5
PORTNO Port number
D3, Internal Pi, Main unit: 1 to 8
External: 1 to 30
5 5 5 6 6 5 6 6 5
ADDRESS1
Upper level address
(group)
D3: 1 to 4
External: 1 to 120
Internal Pi: 1 to 127
Outdoor unit: 1 to 127
Main unit: 1 to 4 (2 to 4 for Port 1)
6 6 6 7 7 6 7 7 6
ADDRESS2
Lower level address
(unit)
D3Dio, D3Di, Indoor unit, Ventilator,
Chiller: 0 to 15
7 8 8 8 8
STARTSTOPMON ON Status Monitor
External Di: 1 to 120
External Dio: ON Status Monitor address 1 to 120
Not specied: 0
NORMALABNORMALMON
Normal/Abnormal
Monitor
Normal/Abnormal Monitor Input address 1 to 120
Not specied: 0
STARTSTOP ON/OFF operation 0: Always 1: Instant
STARTSTOPADDR1 Start/Stop address 1
Always: 1 to 120
Instant: ON address 1 to 120
STARTSTOPADDR2 Start/Stop address 2
Always: Handled as invalid
Instant: OFF address 1 to 120
SERVERINST
BACnet Server Device Instance
0 to 4194302 5 6 5 6
STATOBJTYPE Status Object Type* 0 to 1023, Not used: −1 6 7 6
STATOBJINST Status Object Instance* 0 to 4194302, Not used: −1 7 8 7
OPOBJTYPE Operation Object Type* 0 to 1023, Not used: −1 9 7
OPOBJINST
Operation Object
Instance*
0 to 4194302, Not used: −1 10 8
ERROBJTYPE Error Object Type* 0 to 1023, Not used: −1 8 11
ERROBJINST Error Object Instance* 0 to 4194302, Not used: −1 9 12
ICON Icon ID 100 to 999 7 7 8 9 9 7 5 9 9 7 10 13 8 9
ANADDR ACNSS Address Indoor unit (2 to 128, 1: Invalid) 10
Monitoring
COMMONLV
Communication error monitoring level
1: Monitoring, 2: Monitor + History 8 8 9 10 11 10 10 11 14 9 10
* Set to -1 when not used.
The item is regarded as not used if either the Object Type or Object Instance value is set to –1.
For information on the Object Type, refer to the applicable guideline (ISO16484-5).
Output only when BACnet (optional) is enabled.
Output only when BACnet (optional) is enabled.