DCM601A51 intelligent Touch Manager
31
Acceptable range for each numeric value
Detailed
Type
Classication
Item
For Celsius For Fahrenheit For analog value
Minimum/
Maximum value
(Default value)
Increment
Minimum/
Maximum value
(Default value)
Increment
Minimum/
Maximum value
(Default value)
Increment
External Ai
BACnet Ai
Upper/
Lower
Limit
monitoring
Hysteresis
0.0 to 512.0
(0.0)
0.1
0 to 922
(0)
1
0.00 to
9999.99
(0.00)
0.01
Lower
limit
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)
0.01
Upper
limit
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)
0.01
Analog
value
Minimum
value
−512.0 to 512.0
(0.0/−512.0)
*
3
0.1
−890 to 954
(32/−890)
*
3
1
−9999.99 to
9999.99
(0.00)
0.01
Maximum
value
−512.0 to 512.0
(100.0/512.0)
*
3
0.1
−890 to 954
(212/954)
*
3
1
−9999.99 to
9999.99
(100.00)
0.01
Internal Ai
Upper/
Lower
Limit
monitoring
Hysteresis
0.0 to 512.0
(0.0)
*
2
0.1
0 to 922
(0)
*
2
1
Lower
limit
−512.0 to 512.0
(0.0)
*
2
0.1
−890 to 954
(32)
*
2
1
Upper
limit
−512.0 to 512.0
(0.0)
*
2
0.1
−890 to 954
(32)
*
2
1
BACnet Ao
Analog
value
Min.
of op
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)
*
1
0.01
*
1
Max.
of op
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)
*
1
0.01
*
1
Displayed
accuracy
−1
(−1)
1
0
(0)
1
−2 to 3
(−1)
1
*1 Min of op. and Max of op. can be set up with the accuracy specied in Displayed accuracy.
If Displayed accuracy is modied when Min of op. and Max of op. are already set, their value are rounded to t the
accuracy specied by the Displayed accuracy.
(When loading a CSV le, an input data error will occur if it contains any value ner than the specied accuracy.)
*2 The default values displayed on GUI will change depending on whether Celsius or Fahrenheit is selected in System
Settings.
*3 The former or latter value will be used depending on whether Unit Type is Other or Thermistor, respectively.
(When loading a CSV le with Thermistor selected, the default value will be used regardless of the input data.)