Siemens 6SL3210-1SE27-5UA0 Инструкция по эксплуатации онлайн [66/318] 474597

Siemens 6SL3210-1SE27-5UA0 Инструкция по эксплуатации онлайн [66/318] 474597
Power Modules
3.1 Power Modules Blocksize (PM340)
Manual
66 Manual, 01/2011, 6SL3097-4AC10-0BP2
DANGER
Once all the supply voltages have been disconnected, a hazardous voltage may be present
in the power unit for up to 5 minutes. The cover for the terminals may only be opened after
this time has definitely elapsed.
When opening the protective cover, you must activate the release. A suitable tool (e.g.
screwdriver) must be used for this purpose.
Damaged components must not be used, otherwise this could result in secondary damage
or accidents.
DANGER
The hazard warning in the local language for the DC link discharge time must be affixed to
the component. A set of labels bearing this warning in 16 languages is provided with the
component.
DANGER
The drive components generate high leakage currents in the protective conductor. The
components must only be operated in cabinets or in closed electrical operating areas and
must be connected with the protective conductor. To protect against electric shock, the
protective conductor connection on the cabinet or machine must be implemented in
accordance with one of the following measures:
Fixed connection and protective conductor connection by means of ≥ 10 mm
2
Cu or ≥
16 mm
2
Al
stationary connection and automatic shutdown of the power supply if the protective
conductor is interrupted

Содержание

Похожие устройства

Скачать