Power Modules
3.1 Power Modules Blocksize (PM340)
Manual
Manual, 01/2011, 6SL3097-4AC10-0BP2
67
WARNING
Cooling and mounting clearances for Power Modules
Power Modules must be mounted in the vertical position.
The following clearances must be observed between the components when mounting
1)
:
- frame size FSA: 30 mm (1.18 inch)
- frame size FSB: 40 mm (1.57 inch)
- frame size FSC: 50 mm (1.96 inch)
The following cooling clearances must be observed above and below the component:
- frame sizes FSA and FSB: 100 mm (3.93 inch)
- frame size FSC: 125 mm (4.92 inch)
- frame sizes FSD and FSE: 300 mm (11.81 inch) and
- frame size FSF: 350 mm (13.77 inches).
The following cooling clearances must be observed in front of the component:
- frame sizes FSB to FSF: 30 mm (1.18 inch)
Devices, that could restrict the cooling air flow may not be mounted/installed in this area.
It must be carefully ensured that the cooling air flow of the Power Modules can flow
unrestricted.
1) The Power Modules can be mounted side by side without sub-chassis components up to an ambient temperature of 40 °C.
In combination with sub-chassis components and at ambient temperatures of 40 °C to 55 °C, the specified lateral minimum clearances must
be observed. Where combinations of different frame sizes are concerned, the longer of the two clearances shall apply.
DANGER
Cable shields and unused power-cable cores (e.g. brake cores) must be connected to PE
potential to dissipate capacitive cross-talk charges.
Non-observance can cause lethal shock voltages.