Daikin FXSQ40P7VEB [105/370] Control for heating operation at low outdoor air temperature

Daikin FXZQ20MVET [105/370] Control for heating operation at low outdoor air temperature
SiBE311209 Normal Operation
Function 96
6.6 Control for Heating Operation at Low Outdoor Air
Temperature
To conduct optimal heating operation, the two operation modes, "Two-stage compression" and
"Single-stage compression", are available according to outdoor air temperatures and loads.
System startup
Determination of operation mode
Determine at startup whether to conduct single-stage compression or two-stage compression.
&
· Outdoor air temp. < 5°C
· Capacity of indoor unit
with thermostat ON
> 7.1 to 11.2kW
OR
· Outdoor air temp. 5°C
· Capacity of indoor unit
with thermostat ON
7.1 to 11.2kW
Two-stage compression
OR
· &
· Pc > 3.3MPa
· Function unit compressor = 52Hz
· Outdoor unit compressor
< 104Hz + OFF + OFF
· When (Indoor unit operating capacity ×
Function unit compressor operating capacity)
comes less than a certain value
Single-stage compression
&
· Outdoor unit compressor
> 112Hz + OFF + OFF
· A lapse of 2 min.