SiBE311209 Field Setting
Test Operation 156
(15) Operation of Downward Flow Flap: Yes/No
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
(16) Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Setting Table
Some indoor unit models are not equipped with draft prevention (upward) function.
(17) Setting of the Static Pressure Selection
In the Case of FXDQ
(18) External Static Pressure Settings (for FXMQ model)
The “Second Code No.” is set to 07 (an external static pressure of 100 Pa) at factory setting.
1 The FXMQ50 · 63 · 80 · 100 · 125 · 140PVE cannot be set to 30 Pa.
2 The FXMQ20 · 25 · 32 · 40PVE cannot be set to 180 or 200 Pa.
Mode No. First Code No. Second Code No. Setting
13 (23) 3
01 Down-flow operation: Yes
02 Down-flow operation: No
Mode No. First Code No. Second Code No. Setting
13 (23) 4
01
Upward (Draft
prevention)
02 Standard
03
Downward (Ceiling
soiling prevention)
Model No. First Code No. Second Code No. External static pressure
13 (23) 5
01 Standard (10Pa)
02
High static pressure (30Pa)
Mode No. First Code No. Second Code No.
External Static Pressure
13 (23) 6
01 30Pa (1)
02 50Pa
03 60Pa
04 70Pa
05 80Pa
06 90Pa
07 100Pa
08 110Pa
09 120Pa
10 130Pa
11 140Pa
12 150Pa
13 160Pa
14 180Pa (2)
15 200Pa (2)