Daikin FXSQ40P7VEB [40/370] Specifications

Daikin FXSQ100PVE4 [40/370] Specifications
Specifications SiBE311209
31 Specifications
1-2 ELECTRICAL SPECIFICATIONS FXDQ20M9V3B FXDQ25M9V3B
Power
Supply
Name V1
Phase 1~
Frequency Hz 50
Voltage V 230
Current Minimum circuit amps
(MCA)
A0.2
Maximum fuse amps
(MFA)
A16
Full load amps (FLA) A 0.1
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA < 4 × FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker

Содержание

Скачать