Daikin FXSQ40P7VEB [243/370] Refer to p 05

Daikin FXSQ125PVE4 [243/370] Refer to p 05
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 234
Troubleshooting
Refer to P.305.
Refer to P.315.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Open the stop valve.
+5V
Connector for low pressure sensor
M
icro-computer
A/D input
Make measurement of DC voltage between these wires.
Red
Black
White
Low
pressure
sensor
(4)
(3)
(2)
(1)
(Blue)
1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure. )
2: Make measurement of voltage of the pressure sensor.
CHECK 12
YES
NO
NO
YES
Replace the low pressure sensor.
Replace the main PCB (A1P).
Is the stop
valve open?
(1) Mount a pressure gauge on the low pressure
service port.
(2) Reset the operation using the remote
controller, and then restart the operation.
Are the
characteristics of
the low pressure
sensor normal?
(
1.)
Check if the “low
pressure” value and
the actual
measurement value
by pressure sensor
are the same.
· The low pressure sensor is normal, and the pressure
detected with the PCB is also normal.
· The low pressure has really become low.
Remove the causes by which the low pressure has
become low.
Service Checker
Connect the service checker to compare the “low pressure
value and the actual measurement value by pressure
sensor (1) by using the service checker.
CHECK 2
(X31A)
CHECK 2
CHECK 12