Daikin FXSQ40P7VEB [130/370] Drain pump control

Daikin FXSQ50PVE4 [130/370] Drain pump control
Outline of Control (Indoor Unit) SiBE311209
121 Function
9.3 Drain Pump Control
The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
below).
9.3.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
1. (Normal operation):
The objective of residual operation is to completely drain any moisture adhering to the fin of the
indoor unit heat exchanger when the thermostat goes off during cooling operation.
2. (Error residual):
The remote controller will display "
A3
" and the air conditioner will come to an abnormal stop in 5
minutes if the float switch is turned OFF while the cooling thermo. is ON.
9.3.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF:
3. (Error residual):
The remote controller will display "
A3
" and the air conditioner will come to an abnormal stop if
the float switch is turned OFF and not turned ON again within 5 minutes while the cooling
thermo. is OFF.
Thermostat
(running)
Float switch
Drain pump
ON
OFF
ON
OFF
ON
OFF
Remote controller "
A3
" blinking
abnormal stop
5 min. 5 sec.5 min.
1) Normal operation 2) Error residual
Thermostat
(running)
Float switch
Drain pump
ON
OFF
ON
OFF
ON
OFF
5 min.
5 sec.
5 min.
5 sec.
Enters error treatment if the float switch is not reset within 5 minutes.
Remote controller "
A3
" blinking abnormal stop
3