Daikin FXSQ40P7VEB [225/370] Troubleshooting

Daikin FXZQ32M9V1B [225/370] Troubleshooting
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 216
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Remove the foreign matter.
NO
YES
YES
YES
YES
NO
YES
YES
NO
NO
NO
NO
Connect correctly.
Connect correctly.
Replace the fan PCB (A2P).
Replace the fan motor.
Replace the fan motor.
Turn OFF the power and wait for
10 minutes.
There is a foreign
matter around the
fan.
The fan motor
connectors (X1A and
X2A) of the fan PCB
(A2P) are disconnected.
The connectors
between the indoor unit
PCB (A1P) and the fan
PCB (A2P) are
disconnected.
The fuse (F3U,
white) on the fan
PCB (A2P) has no
continuity.
The fan can be moved
lightly by hand after the
fan motor connector of the
fan PCB (A2P) is
removed.
The resistance between
the power wire terminals
of the fan motor and motor
frame (metal part) is 1 M
or below.
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases (1).