Daikin FXSQ40P7VEB [296/370] Troubleshooting

Daikin FXSQ80PVE4 [296/370] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE311209
287 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Correct the transmission wiring
with the external control adaptor
for outdoor unit.
Check if any disconnection or
connection error is detected in
transmission wiring external
control adaptor for outdoor
unit.
Confirmation of
error 3
Confirmation of
error 4
Diagnosis Flow 1
Check if the normal
condition monitor LED
for the outdoor unit
PCB blinks.
Check if power is
supplied to the
outdoor units.
Check if the normal
condition monitor LED
for the external control
adaptor for outdoor
unit blinks.
Check if the power supply
wire for the external control
adaptor for outdoor unit is
connected to 5V supply
line.
YES
NO
NO
NO
YES YES
NONO
YES
YES
Supply the power to the outdoor
unit.
Replace the outdoor unit main
PCB.
Connect the power supply wire
for the external control adaptor
for outdoor unit to 5V supply
line.
Replace the PCB of the external
control adaptor for outdoor unit.
Replace the outdoor unit main
PCB.