Troubleshooting by Indication on the Remote Controller SiBE311209
263 Service Diagnosis
4.36 Inverter Radiation Fin Temperature Rise Error
Remote
Controller
Display
L4
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Error Decision
Conditions
When the temperature of the inverter radiation fin increases 87°C or more.
Supposed
Causes
Actuation of radiation fin thermal (Actuates above 87°C)
Defective inverter PCB
Defective radiation fin thermistor
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
While in monitor mode,
check the unit concerned.
The radiation fin of the
inverter PCB concerned
exceeded a temperature
of 87°C.
YES
NO
Turn OFF the power supply,
and then make measurement
of resistance of the radiation
fin thermistor.
Is the thermistor
resistance
normal?
CHECK 11
NO
YES
Connect and disconnect the
connector (X111A) for the
radiation fin thermistor, and
then properly connect it.
Does the error recur
when the power supply
turns ON to start the
compressor?
YES
NO
Defective radiation fin from the
power unit
• Blocked suction air port
• Stained radiation fin
• High outdoor air temperature
Replace the thermistor.
Replace the compressor inverter
PCB.
Continue the operation.
z
It is supposed that the radiation
fin temperature became high due
to some field factors. In this
connection, check the following
points:
Stained radiation fin
Airflow obstructed with dirt or
foreign matters
Damage to fan propellers
Too high outdoor air
temperature
CHECK 11