Daikin FXSQ40P7VEB [260/370] Heat exchanger gas pipe temperature thermistor r2t

Daikin FXSQ125P7VEB [260/370] Heat exchanger gas pipe temperature thermistor r2t
Troubleshooting by Indication on the Remote Controller SiBE311209
251 Service Diagnosis
4.27 Heat Exchanger Gas Pipe Temperature Thermistor (R2T)
Remote
Controller
Display
J4
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Detect error based on the temperature detected by heat exchanger gas pipe temperature
thermistor.
Error Decision
Conditions
In operation, when a thermistor is disconnected or short circuits.
Supposed
Causes
Defective connection of thermistor
Defective temperature heat exchanger gas pipe thermistor
Defective outdoor unit PCB
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connector is
connected to X30A
of outdoor unit
PCB (A1P).
NO
YES
Resistance is normal when
measured after disconnecting
the thermistor (R2T) from the
outdoor unit PCB.
CHECK 11
NO
YES
Connect the connector and turn ON
again.
Replace the thermistor (R2T)
Replace the outdoor unit PCB
(A1P).
CHECK 11