89 Function
5.3 Startup Control of Function Unit (only for heating
operation at low outdoor air temperature)
Part name
Electric
symbol
Pressure
equalization
control before
startup
Startup control
Step 1 Step 2 Step 3 Step 4
Compressor M1C 0Hz 52 Hz 52 Hz 112 Hz 180 Hz
Electronic expansion
valve (liquid injection)
Y1E 0 pls 0 pls 0 pls PI control PI control
Electronic expansion
valve (two-stage
switching-1)
Y2E1 0 pls 0 pls 200 pls 200 pls 760 pls
Electronic expansion
valve (two-stage
switching-2)
Y2E2 0 pls 0 pls 0 pls 0 pls 760 pls
Solenoid valve (hot
gas)
Y1S ON ON OFF OFF OFF
Solenoid valve (two-
stage decompression)
Y2S OFF OFF OFF ON ON
Solenoid valve
(bypass-1)
Y3SONONONOFFOFF
Solenoid valve
(bypass-2)
Y4SONONONOFFOFF
Solenoid valve (liquid
line switch)
Y5SONONONOFFOFF
Ending conditions
A lapse of
30 sec.
A lapse of
30 sec.
A lapse of
10 sec.
A lapse of
30 sec.
A lapse of
20 sec.