Daikin FXSQ40P7VEB [219/370] Drain level control system s1l abnormality

Daikin FXSQ63P7VEB [219/370] Drain level control system s1l abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 210
4.3 Drain Level Control System (S1L) Abnormality
Remote
Controller
Display
A3
Applicable
Models
FXCQ, FXZQ, FXFQ, FXSQ, FXKQ, FXDQ, FXMQ, FXUQ, FXHQ (Option), FXMQ200 · 250MA
(Option), FXAQ (Option)
Method of Error
Detection
By float switch OFF detection
Error Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF
Supposed
Causes
220~240V power supply is not provided
Defective float switch or short circuit connector
Defective drain pump
Drain clogging, upward slope, etc.
Defective indoor unit PCB
Loose connection of connector