Daikin FXSQ40P7VEB [337/370] Fxkq ma fxhq ma fxlq ma fxnq ma fxmq ma

Daikin FXZQ20MVE4 [337/370] Fxkq ma fxhq ma fxlq ma fxnq ma fxmq ma
SiBE311209 Piping Diagrams
Appendix 328
FXKQ-MA, FXHQ-MA, FXLQ-MA, FXNQ-MA, FXMQ-MA
4D034245G
Heat exchanger
(4)
Fan
(2)
(3)
(1)
Filter
Filter
Electronic
expansion valve
Gas piping connection port
Flare connection : φ15.9 or less
Attached piping : Above φ19.1
Liquid piping connection port
(Flare connection)
M
Code Name Code Main function
(1) Electronic expansion valve Y1E
Used for gas superheated degree control while in
cooling operation or subcooled degree control while
in heating operation.
(2)
Suction air temperature
thermistor
R1T Used for thermostat control.
(3) Liquid pipe thermistor R2T
Used for gas superheated degree control while in
cooling operation or subcooled degree control while
in heating operation.
(4) Gas pipe thermistor R3T
Used for gas superheated degree control while in
cooling operation.
(mm)
Capacity GAS Liquid
20 / 25 / 32 / 40 / 50MA φ12.7 φ6.4
63 / 80 / 100 / 115MA φ15.9 φ9.5
200MA φ19.1 φ9.5
250MA φ22.2 φ9.5

Содержание

Скачать