SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 296
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor unit main PCB.
Confirmation of
error 3
Confirmation of
error 4
YES
NO
Diagnosis Flow 3
YES
NO
NO
YES
YES
NO
Check if the
outdoor unit
PCB is replaced
with PCB for
spare.
Is a correct spare
PCB procured?
Check if the spare
PCB setting is
correct.
Check if the unit
is not connected
to outdoor units
of different
models.
Check the model of the outdoor
unit.
Replace it with the correct spare
PCB.
Correct the setting to reset the
power.
Replace the spare PCB.
NO
YES
Confirmation of
error 3
Confirmation of
error 4
Diagnosis Flow 4
Is the model BP
connected?
Connect the indoor units correctly.
Replace the outdoor unit PCB.