Daikin FXSQ40P7VEB [217/370] Troubleshooting by indication on the remote controller

Daikin FXHQ32MVE [217/370] Troubleshooting by indication on the remote controller
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 208
4. Troubleshooting by Indication on the Remote
Controller
4.1 Error of External Protection Device
Remote
Controller
Display
A0
Applicable
Models
All indoor unit models
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF input"
Supposed
Causes
Actuation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Actuation of external protection
device.
Change the second code No. to
"01" or "02".
Replace the indoor unit PCB.
YES
YES
NO
NO
External protection
device is connected to
terminals T1 and T2 of
the indoor unit terminal
block.
ON/OFF input
External (mode No.
12, first code No. 1)
has been set to
external protection
device input (second
code No. 03) by
remote controller.
Check the setting state of the
ON/OFF input external by
remote controller.