Test Operation SiBE311209
137 Test Operation
12.In case leak detection function is required
Press the BS4 TEST button once for post-processing with regard to the leak detection
function and press the BS1 MODE button to confirm that charging is completed.
Record the amount that was added on the additional refrigerant charge label provided with
the unit and attach it on the back side of the front panel.
Perform the procedure "1.3.4 Procedure for Inputting the Additional Refrigerant Charge
Weight into the PCB" as described on P.140.
12.In case leak detection function is not required
Press the BS1 MODE button once and the charging is complete.
Record the amount that was added on the additional refrigerant charge label provided with
the unit and attach it on the back side of the front panel.
Perform the procedure "1.3.4 Procedure for Inputting the Additional Refrigerant Charge
Weight into the PCB" as described on P.140.
<Charging in cooling mode>
8. Startup
Wait while the unit is preparing for charging in cooling mode.
It takes about 2 to 10 minutes for the system to become stable.
In case of a small charging amount, the system will start charging the refrigerant before the
system reaches the stable state. It may disturb a correct decision and may cause
overcharging.
9. Ready
Press the BS4 TEST button once within 5 minutes.
If the BS4 TEST button is not pressed within 5 minutes, "
P2
" will be displayed on the remote
controller. Refer to "3. Remote controller error code display" on P.140.
10.Operation
When the following LED display is shown, open valve A and close the front panel. If the front
panel is left open, the system can not operate properly during the refrigerant charging.
= The state of this LED is not important.
Note 1: When the refrigerant tank is not connected or is left with the valve closed for 30 minutes or
more, the outdoor unit will stop operation and the "
P2
" code will be displayed on the remote
controller of the indoor unit. Follow the procedure as described in "3. Remote controller error
code display" on P.140.
Note 2: When an error occurs, check the display of the remote controller and refer to "3. Remote
controller error code display" on P.140.
H1P H2P H3P H4P H5P H6P H7P
Pressure control
(for the first minute)
hlhhhhk
Startup control
(for the next 2 minutes)
hlhhhkh
Waiting for stable cooling
conditions
(for the next ±15 minutes
(according to the system))
hlhhhkk
H1P H2P H3P H4P H5P H6P H7P
lllhkhk
H1P H2P H3P H4P H5P H6P H7P
kl ∗∗∗∗∗