Startup Control SiBE311209
87 Function
5. Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to liquid refrigerant return or else after the startup, the following
control is made and the position of the four way valve is also determined. To position the four way valve, the master and
slave units simultaneously startup.
5.1 Startup Control in Cooling Operation
Actuator Symbol
Electric
symbol
Pressure
equalization
control
before startup
Startup control
STEP1 STEP2
Compressor 1
M1C
0 Hz 52 Hz + OFF + OFF
52Hz + OFF + OFF + 2STEP /
20 sec.
(Until it reaches
Pc - Pe > 0.39 MPa)
Compressor 2 M2C
Compressor 3 M3C
Outdoor unit fan 1
M1F
STEP4
Ta < 20°C: OFF
Ta 20°C: STEP4
+1step/15 sec. (When
Pc_max > 2.16 MPa)
-1step/15 sec. (When
Pc_max < 1.77 MPa)
Outdoor unit fan 2 M2F
Electronic expansion
valve (Main)
EVM Y1E 0 pls 480 pls 480 pls
Electronic expansion
valve (Subcooling)
EVT Y3E 0 pls 0 pls 0 pls
Electronic expansion
valve (Refrigerant
charge)
EVJ Y2E 80 pls 80 pls 80 pls
Solenoid valve
(Refrigerant regulator gas
vent pipe)
SVG Y1S OFF OFF OFF
Four way valve
(Heat exchanger switch)
20SA Y3S OFF OFF OFF
Solenoid valve
(Refrigerant regulator
liquid pipe)
SVL Y4S OFF OFF OFF
Solenoid valve (Hot gas) SVP Y5S OFF OFF OFF
Solenoid valve (Main
bypass)
SVE Y6S OFF ON ON
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVO Y7S OFF OFF OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVT Y8S OFF OFF OFF
Solenoid valve (Heat
exchanger hot gas)
SVHG Y9S ON ON ON
Four way valve (High/low
pressure gas pipe switch)
20SB Y2S ON ON ON
Ending conditions
A lapse of 60
sec.
A lapse of 15 sec.
A lapse of 90 sec.
Pc - Pe > 0.39 MPa
OR