Daikin FXSQ40P7VEB [298/370] Troubleshooting

Daikin FXSQ80PVE4 [298/370] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE311209
289 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Confirmation of
error 3
Diagnosis Flow 3
Confirmation of
error 4
Check the connection status of
connecting wires of Multi Slave 1 with
outdoor multi. Check if the wiring is
disconnected or is about to be
disconnected.
YES
NO
Correct the transmission wires of
the outdoor multi and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P) of the Multi Slave 1.
Confirmation of
error 3
Diagnosis Flow 4
Confirmation of
error 4
Check the connection status of
connecting wires of Multi Slave 2 with
outdoor multi. Check if the wiring is
disconnected or is about to be
disconnected.
YES
NO
Correct the transmission wires of
the outdoor multi and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P) of the Multi Slave 2.
Confirmation of
error 3
Diagnosis Flow 5
Confirmation of
error 4
Check if the outdoor
unit RTSQ8~16PAY1 is
connected to multi-
system.
YES
NO
Remove the transmission wires of
the outdoor multi and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P).