Field Setting SiBE311209
159 Test Operation
BRC7C Type
BRC7E Type
BRC4C Type
Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, press “ ” button for 4 seconds or more, and operation then
enters the “field setting mode.”
2. Set mode No. “00” with “ ” button.
3. Set the group No. for each group with “ ” “ ” button (advance/backward).
4. Enter the selected group numbers by pressing “ ” button.
5. Press “ ” button and return to the normal mode.
BRC2A Type
BRC2C Type
Group No. setting by simplified remote controller for centralized control.
1. Dismount the upper casing from the remote controller.
2. Press the [BS6] button (2) (field setting) to set the system to field setting mode.
3. Press the [BS2] button (3) (temperature setting " ") or the [BS3] (3) temperature setting
" ") to set the Mode No. to "00".
4. Press the [BS9] button (4) (setting A) or the [BS10] button (4) (setting B) to select a Group
No.
(The group numbers increase like 1-00, 1-01, · · · 1-15, 2-00, · · ·, 4-15. However, the ON/
OFF controller only displays group numbers in the range selected by the control range
setting switch.)
5. Press the [BS7] button (5) (setting/cancel) to determine the Group No. selected.
6. Press the [BS6] button (2) (field setting) to return the system to normal mode.
<CAUTION>
z
Even if no remote controller is used, connect a remote controller to make Group No. setting,
make setting of Group No. for centralized control, and then disconnect the remote controller
after the completion of setting.
z
To make Group No. setting, turn on the power supply of the central remote controller, ON/
OFF controller, and indoor unit, respectively.
MODE NO.
FIELD SETTING MODE
3
4
GROUP NO.
2
1, 5
MODE NO.
UNIT NO.
(3)
Group NO.
(3)
(8)(2) (7) (4) (5) (6)