SiBE37-704_A Test Operation
Test Operation 170
When a malfunction occurs, check the display of the remote controller and refer to "3. Remote
controller malfunction code display" on page 172.
9. Complete
If the calculated amount of refrigerant is reached, close valve A and press the BS3 RETURN
button once.
Note: Always close valve A and remove the refrigerant tank immediately after finishing the refrigerant
charge operation.
Beware of the fan blades when you open the front panel.
The fan may still rotate for a while after unit operation has stopped.
10.In case leak detection function is required
Press the BS4 TEST button once for post-processing with regard to the leak detection
function and press the BS1 MODE button to confirm that charging is completed.
Record the amount that was added on the additional refrigerant charge label provided with
the unit and attach it on the back side of the front panel.
Perform the procedure " 1.2.5.6 Procedure for inputting the additional refrigerant charge
weight into the PCB" as described on page 172.
10.In case leak detection function is not required
Press the BS1 MODE button once and the charging is complete.
Record the amount that was added on the additional refrigerant charge label provided with
the unit and attach it on the back side of the front panel.
Perform the procedure " 1.2.5.6 Procedure for inputting the additional refrigerant charge
weight into the PCB" as described on page 172.
<Charging in cooling mode>
6. Start up
Wait while the unit is preparing for charging in cooling mode.
It takes about 2 to 10 minutes for the system to become stable.
In case of a small charging amount, the system will start charging the refrigerant before the
system reaches the stable state. It may disturb a correct decision and may cause
overcharging.
7. Ready
Press the BS4 TEST button once within 5 minutes.
If the BS4 TEST button is not pushed within 5 minutes,
P2
will be displayed on the remote
controller. Refer to "3. Remote controller malfunction code display" on page 172.
8. Operation
When the following LED display is shown, open valve A and close the front panel. If the front
panel is left open, the system can not operate properly during the refrigerant charging.
When the refrigerant tank is not connected or is left with the valve closed for 30 minutes or
more, the outdoor unit will stop operation and the
P2
code will be displayed on the remote
controller of the indoor unit. Follow the procedure as described in "3. Remote controller
malfunction code display" on page 172.
H1P H2P H3P H4P H5P H6P H7P
lllkkkk
H1P H2P H3P H4P H5P H6P H7P
Pressure control
(for the first minute)
hlhhhhk
Start up control
(for the next 2 minutes)
hlhhhkh
Waiting for stable cooling
conditions
(for the next ±15 minutes
(according to the system))
hlhhhkk
H1P H2P H3P H4P H5P H6P H7P
lllhkhk